  digital temperature controllers e5cn/e5cn-u 1 digital temperature controllers e5cn/e5cn-u this best-selling general-purpose 48  48-mm temperature controller is now even better. easy, dependable, co mplete functionality, and 11-segment displays. ? controllers now available with analog inputs.  faster sampling at 250 ms.  transfer output provided for easy output to recorders.  voltage outputs (to drive ssrs) for both heating and cooling control. can be used for alarms to provide three alarm outputs.  models available with three-phase heater burnout detection and ssr fault detection.  easy setting with 11-segment displays.  connect to either a thermocouple or platinum resistance thermometer with the same model.  easily see the status from a distance with pv display with three- color switching function.  setting protection indicator informs operator when protection is enabled.  manual output provided.  controller available with long-life relay output (available soon). note: refer to precautions on page 21. note: refer to page 19 for information on changes in comparison to previous models. features improved functions for a wider range of application control analog values, such as pressures, flowrates, and levels the new e5cn series now also includes models that accept analog inputs, enabling control applications other than for temperature, including pressure, flowrate, level, humidity, and weight control. note: e5cn- @ l (models with analog inputs) faster sampling at 250 ms the previous sampling time of 500 ms has been reduced by half to 250 ms. this enables the new e5cn to handle application requiring even greater response speed and accuracy. easy connector to a recorder a transfer output now makes it easy to connect to a recorder or plc analog i/o unit. note: e5cn-c @ (models with current outputs) voltage outputs (to drive ssrs) for both heating and cooling control. can be used for alarms to provide three alarm outputs. voltage outputs can be used for both heating and cooling for models with two control outputs. also, control output 2 can be set for use as an alarm output, to enable using up to three alarm outputs. note: e5cn- @ q (option board) three-phase heater burnout detection with models with three-phase heater burnout and ssr failure detection, two current transformers can be connected to detect both heater burnout and ssr failure at the same time, reducing costs because a separate heater burnout alarm device is not required. ssr failure detection can be used even with models with single- phase heater burnout alarms. note: e5cn- @ hh @ (option board) easy, dependable, and even faster easy setting with 11-segment displays the new e5cn features 11-segment displays to make text easier to read, eliminating the need to decode displays when trying to set parameters, as was necessary with previous temperature controllers. multi-input capability with one controller connect to either a thermocouple or platinum resistance thermometer with the same model. model selection is simplified, stocks are reduced, and fewer ma intenance parts are required. easily see status from a distance with pv display with three-color switching function setting protection indicator informs operator when protection is enabled a special icon on the display panel lights to let the operator know when setting protection has been set.
2 digital temperature controllers e5cn/e5cn-u model number structure model number legend 1. output type r: relay q: voltage (for driving ssr) c: current y: long-life relay output (available soon) 2. number of alarms blank: no alarm 2: two alarms 3. option unit m: option unit can be mounted 4. input type t: thermocouple/platinum resistance thermometer (multi-input) l: analog input 1 2 3 4 e5cn- @@ m @ -500 this data sheet is provided as a guideline for selecting products. be sure to refer to the following user manuals for applicati on precautions and other information required for operati on before attempting to use the product. e5cn/e5cn-u temperature controller user's manual (cat. no. h129) e5cn temperature controller communica tions user's manual (cat. no. h130)
digital temperature controllers e5cn/e5cn-u 3 ordering information controllers with temperature inputs (multi-input) controllers with analog inputs option units the e5cn provides optional functionality when one of the following option units is mounted. note: option units cannot be used for plug-in models. these option units can be used for the new e5cn models only. size power supply voltage number of alarm points control outputs model 1/16 din 48  48  78 (w  h  d) 100 to 240 vac 0 relay e5cn-rmt-500 voltage (for driving ssr) e5cn-qmt-500 current e5cn-cmt-500 2 relay e5cn-r2mt-500 voltage (for driving ssr) e5cn-q2mt-500 current e5cn-c2mt-500 long-life relay e5cn-y2mt-500 24 vac/dc 0 relay e5cn-rmt-500 voltage (for driving ssr) e5cn-qmt-500 current e5cn-cmt-500 2 relay e5cn-r2mt-500 voltage (for driving ssr) e5cn-q2mt-500 current e5cn-c2mt-500 long-life relay e5cn-y2mt-500 size power supply voltage number of alarm points control outputs model 1/16 din 48  48  78 (w  h  d) 100 to 240 vac 0 relay e5cn-rml-500 voltage (for driving ssr) e5cn-qml-500 current e5cn-cml-500 2 relay e5cn-r2ml-500 voltage (for driving ssr) e5cn-q2ml-500 current E5CN-C2ML-500 long-life relay e5cn-y2ml-500 24 vac/dc 2 relay e5cn-r2ml-500 voltage (for driving ssr) e5cn-q2ml-500 current E5CN-C2ML-500 functions model communications heater burnout/ssr failure detection e53-cnh03n communications e53-cn03n heater burnout/ssr failure detection event inputs e53-cnhbn event inputs e53-cnbn communications 3-phase heater burnout /ssr failure detection e53-cnhh03n communications control output 2 (voltage output) e53-cnq03n heater burnout/ssr failure detection control output 2 (voltage output) e53-cnqhn ct1 e53-cnqhn control output 2/ ct ? + 12 11 15 14 13 e53-cnq03n communications/ control output 2 ? + b a rs-485 12 11 15 14 13 e53-cnhh03n communications/ two cts ct2 ct1 13 14 15 11 12 b a rs-485 e53-cn03n communications do not use. do not use. do not use. do not use. do not use. b a rs-485 12 11 15 14 13 e53-cnbn event inputs ev1 ev2 12 11 15 14 13 e53-cnhbn event inputs/ ct ct1 13 14 15 11 12 ev2 ev1 attach the appropriate terminal labels. e53-cnh03n communications/ ct ct1 13 14 15 11 12 b a rs-485 do not use. do not use. do not use. control output 2 control output 2 12 vdc, 21 ma voltage output
4 digital temperature controllers e5cn/e5cn-u model number structure model number legend (plug-in-type controllers) 1. output type r: relay q: voltage 2. number of alarms blank: no alarm 1: one alarm 2: two alarms 3. input type t: thermocouple/platinum resistance thermometer (multi-input) 4. plug-in type u: plug-in type ordering information (plug-in-type controllers) controllers with temperature inputs (multi-input) note: option units (e53-cn @@ n) cannot be used for plug-in models. accessories (order separately) terminal cover current transformers (cts) adapter note: use this adapter when the panel has been previously prepared for the e5b @ . sockets (for models with plug-in connectors) 1 2 3 4 e5cn- @@@ u size power supply voltage number of alarm points control outputs model 1/16 din 48  48  78 (w  h  d) 100 to 240 vac 0 relay e5cn-rtu voltage (for driving ssr) e5cn-qtu 1 relay e5cn-r1tu voltage (for driving ssr) e5cn-q1tu 2 relay e5cn-r2tu voltage (for driving ssr) e5cn-q2tu 24 vac/dc 0 relay e5cn-rtu voltage (for driving ssr) e5cn-qtu 1 relay e5cn-r1tu voltage (for driving ssr) e5cn-q1tu 2 relay e5cn-r2tu voltage (for driving ssr) e5cn-q2tu connectable models terminal type model e53-cov10 model e54-ct1 e54-ct3 hole diameter 5.8 dia. 12.0 dia. connectable models terminal type model y92f-45 model p2cf-11 p2cf-11-e p3ga-11 y92a-48g type front- connecting socket front- connecting socket with finger protection back- connecting socket terminal cover for finger protection
digital temperature controllers e5cn/e5cn-u 5 specifications ratings item power supply voltage 100 to 240 vac, 50/60 hz 24 vac, 50/60 hz or 24 vdc operating voltage range 85% to 110% of rated supply voltage power consumption e5cn 7.5 va max. (e5cn-r2t: 3.0 va at 100 vac) 5 va/3 w max. (e5cn-r2t: 2.7 va at 24 vac) e5cn-u 6 va max. 3 va/2 w max. sensor input models with temperature inputs thermocouple: k, j, t, e, l, u, n, r, s, or b platinum resistance thermometer: pt100 or jpt100 infrared temperature sensor: 10 to 70  c, 60 to 120  c, 115 to 165  c, or 160 to 260  c voltage input: 0 to 50 mv models with analog inputs current input: 4 to 20 ma or 0 to 20 ma voltage input: 1 to 5 v, 0 to 5 v, or 0 to 10 v input impedance current input: 150  , voltage input: 1 m  (use a 1:1 connection when connecting the es2-hb.) control output relay output e5cn spst-no, 250 vac, 3 a (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 v, 10 ma e5cn-u spdt, 250 vac, 3 a (resistive load), electric al life: 100,000 operations, minimum applicable load: 5 v, 10 ma vo l tag e o u tp ut e5cn e5cn-u output voltage: 12 vdc  15% (pnp), max. load current: 21 ma, with short-circuit protection circuit current output e5cn 4 to 20 ma dc/0 to 20 ma dc, load: 600  max., resolution: approx. 2,700 long-life relay output e5cn spst-no, 250 vac, 3 a (resistive load), electrical life: 1,000,000 operations, minimum applicable load: 5 v, 100 ma (do not connect a dc load.) alarm output spst-no, 250 vac, 1 a (resistive load), electrical life: 100,000 operations, minimum applicable load: 1 v, 1 ma event input contact input on: 1 k  max., off: 100 k  min. non-contact input on: residual voltage: 1.5 v max., off: leakage current: 0.1 ma max. outflow current: approx. 7 ma per point control method on/off control or 2-pid control (with auto-tuning) setting method digital setting using front panel keys indication method 11-segment digital display and individual indicators (7-segments displays also possible) character height: pv: 11 mm, sv: 6.5 mm other functions manual output, heating/cooling control, transfer output (on some models), loop break alarm, multi sp, mv limiter, input digital filter, self-tuning, temperatur e input shift, run/stop, protection functions, etc. ambient operating temperature  10 to 55  c (with no icing or condensati on), for 3-year warranty:  10 to 50  c ambient operating humidity 25% to 85% storage temperature  25 to 65  c (with no icing or condensation)
6 digital temperature controllers e5cn/e5cn-u input ranges thermocouples/platinum resistance thermometers (multi-inputs) models with analog inputs input type platinum resistance thermometer thermocouple infrared temperature sensor analog input name pt100 jpt100 k j t e l u n r s b 10 to 70  c 60 to 120  c 115 to 165  c 160 to 260  c 0 to 50 mv 1800 1700 1600 1500 1400 1300 1200 1100 1000 900 800 700 600 500 400 300 200 100 0  100.0  200.0 1800 usable in the following ranges by scaling:  1999 to 9999 or  199.9 to 999.9 1700 1700 1300 1300 850 850 850 600 500.0 500.0 500.0 400.0 400 400.0 400 400.0 260 120 165 100.0 100.0 90 100 0.0 0.0 0 0 0 0 0 0 0  20.0  100  20.0  100  200  199.9  199.9  200  200  199.9  200  199.9  200 setting number 01234 5 6 7 8 9 1011121314151617181920 21 22 23 temperature range (  c) the applicable standards for the input types are as follows: k, j, t, e, n, r, s, b: iec584-1 l: fe-cuni, din 43710-1985 u: cu-cuni, din 43710-1985 pt100: iec 751 shaded settings are the default settings. input type current voltage input specification 4 to 20ma 0 to 20 ma 1 to 5 v 0 to 5 v 0 to 10 v setting range usable in the following ranges by scaling:  1999 to 9999,  199.9 to 999.9,  19.99 to 99.99 or  1.999 to 9.999 setting number 01234sha ded settings are the default settings.
digital temperature controllers e5cn/e5cn-u 7 alarm types select alarm types out of the 12 alarm types listed in the following table. note: 1. with set values 1, 4 and 5, the upper and lower limit values can be set independently for each alarm type, and are expressed as ?l? and ?h.? 2. set value: 1, upper- and lower-limit alarm 3. set value: 4, upper- and lower-limit range 4. set value: 5, upper- and lower-limit with standby sequence for upper- and lower-limit alarm described above ? case 1 and 2 always off when the upper-limit and lower-limit hysteresis overlaps.  case 3: always off 5. set value: 5, upper- and lower-limit with standby sequence always off when the upper-limit and lower-limit hysteresis overlaps. 6. set value: 12, lba can be set only for alarm 1. set the alarm types for alarms 1 to 3 independently in the initial setting level. the default setting is 2 (upper limit). set value alarm type alarm output operation when x is positive when x is negative 0 alarm function off output off 1 (see note 1.) upper- and lower- limit (see note 2.) 2 upper limit 3lower limit 4 (see note 1.) upper- and lower- limit range (see note 3.) 5 (see note 1.) upper- and lower- limit with standby sequence (see note 5.) (see note 4.) 6 upper-limit with standby sequence 7 lower-limit with standby sequence 8 absolute-value upper-limit 9 absolute-value lower-limit 10 absolute-value upper-limit with standby sequence 11 absolute-value lower-limit with standby sequence 12 (see note 6.) lba (for alarm 1 only) --- on off sp lh sp x on off sp x on off sp x on off sp x on off sp lh on off sp lh on off sp x on off sp x on off sp x on off sp x on off 0 x on off 0 x on off 0 x on off 0 x on off 0 x on off 0 x on off 0 x on off 0 x on off lh h < 0, l > 0 | h | < | l | sp case 1 lh h > 0, l < 0 | h | > | l | sp case 2 l h h < 0, l < 0 sp l h h < 0, l > 0 | h | | l | sp l h h > 0, l < 0 | | | l | < 0, l > 0 | h | < | l | sp case 1 lh h > 0, l < 0 | h | > | l | sp case 2 l h h < 0, l < 0 sp l l h h < 0, l > 0 | h | | l | sp h h > 0, l < 0 | h | | l | sp case 3 (always on)
8 digital temperature controllers e5cn/e5cn-u characteristics note: 1. the indication of k thermocouples in the  200 to 1300  c range, t and n thermocouples at a temperature of  100  c max., and u and l thermocouples at any temperature is  2  c  1 digit maximum. the indication accuracy of the b thermocouple at a temperature of 400  c max. is not specified. the indication accuracy of the r and s thermocouples at a temperature of 200  c max. is  3  c  1 digit max. 2. ?eu? stands for engineering unit and is used as the unit after scaling. for a temperature sensor, the eu is  c or  f. 3. when robust tuning (rt) is on, the differential time is 0.0 to 999.9 (in units of 0.1 s). 4. b, r, and s sensors: 0.2  c/  max. (100  max.) communications specifications note: the baud rate, data bit length, stop bit length, and vertical parity can be individually set using the communications setting level. current transformer (sold separately) ratings indication accuracy thermocouple: (see note 1.) e5cn: (  0.5% of indicated value or  1  c, whichever is greater)  1 digit max. e5cn-u: (  1% of indicated value or  2  c, whichever is greater)  1 digit max. platinum resistance thermometer: (  0.5% of indicated value or  1  c, whichever is greater)  1 digit max. analog input:  0.5% fs  1 digit max. ct input:  5% fs  1 digit max. hysteresis models with thermocouple/platinum resistance thermometer (multi-input) input: 0.1 to 999.9 eu (in units of 0.1 eu) models with analog input: 0.01 to 99.99% fs (in units of 0.01% fs) proportional band (p) models with thermocouple/platinum resistance thermometer (multi-input) input: 0.1 to 999.9 eu (in units of 0.1 eu) models with analog input: 0.1 to 999.9% fs (in units of 0.1% fs) integral time (i) 0 to 3999 s (in units of 1 s) derivative time (d) 0 to 3999 s (in units of 1 s) (see note 3.) control period 0.5, 1 to 99 s (in units of 1 s) manual reset value 0.0 to 100.0% (in units of 0.1%) alarm setting range  1999 to 9999 (decimal point position depends on input type) sampling period 250 ms affect of signal source resistance thermocouple: 0.1  c/  max. (100  max.) (see note 4.) platinum resistance thermometer: 0.4  c/  max. (10  max.) insulation resistance 20 m  min. (at 500 vdc) dielectric strength 2,000 vac, 50 or 60 hz for 1 min (between terminals with different charge) vibration resistance malfunction 10 to 55 hz, 20 m/s 2 for 10 min each in x, y, and z directions destruction 10 to 55 hz, 0.75-mm single amplitude for 2 hrs each in x, y, and z directions shock resistance malfunction 100 m/s 2 min., 3 times each in x, y, and z directions destruction 300 m/s 2 min., 3 times each in x, y, and z directions weight e5cn controller: approx. 150 g, mounting bracket: approx. 10 g e5cn-u controller: approx. 110 g, mounting bracket: approx. 10 g degree of protection e5cn front panel: nema4x for indoor use (equivalent to ip66) rear case: ip20, terminal section: ip00 e5cn-u front panel: equivalent to ip50, rear case: ip20, terminals: ip00 memory protection non-volatile memory (number of writes: 1,000,000 operations) transmission line connection method rs-485 multipoint communications rs-485 (two-wire, half duplex) synchronization method start-stop synchronization baud rate 1200, 2400, 4800, 9600, 19200, or 38400 bps transmission code ascii data bit length 7 or 8 bits stop bit length 1 or 2 bits error detection vertical parity (none, even, odd) frame check sequence (fcs) with sysway block check character (bcc) with compoway/f or crc-16 modbus flow control none interface rs-485 retry function none communications buffer 40 bytes communications response wait time 0 to 99 ms default: 20 ms dielectric strength 1,000 vac for 1 min vibration resistance 50 hz, 98 m/s 2 weight e54-ct1: approx. 11.5 g, e54-ct3: approx. 50 g accessories (e54-ct3 only) armatures (2) plugs (2)
digital temperature controllers e5cn/e5cn-u 9 heater burnout alarms and ssr failure detection alarms (e5cn models with heater burnout and ssr failure detection alarms) note: 1. if the on time of control output 1 is less than 190 ms, heater burnout detection and the heat er current will not be measured. 2. if the off time of control output 1 is less than 190 ms, ssr failure detection and the heater current will not be measured. electrical life expectancy curve for relays (reference values) note: do not connect a dc load to a controller with a long-life relay output. maximum heater current 50 a ac input current indication accuracy  5% fs  1 digit max. heater burnout alarm setting range 0.1 to 49.9 a (in units of 0.1 a) 0.0 a: heater burnout/ssr failure alarm output turned off. 50.0 a: heater burnout/ssr failure alarm output turned on. minimum detection on time: 190 ms (see note 1.) ssr failure detection alarm setting range 0.1 to 49.9 a (in units of 0.1 a) 0.0 a: heater burnout/ssr failure alarm output turned on. 50.0 a: heater burnout/ssr failure alarm output turned off. minimum detection off time: 190 ms (see note 2.) 500 300 100 50 30 10 5 3 1 0123456 switching current (a) life ( 10 4 operations) e5cn 250 vac, 30 vdc (resistive load) cos = 1
10 digital temperature controllers e5cn/e5cn-u external connections  a voltage output (control output) is not electrically insulated from the internal circuits. when using a grounding thermocouple , do not connect any of the control output terminals to gr ound. if the control output terminals are connected to ground, errors will occur in th e measured temperature values as a result of leakage current.  standard insulation is applied between any of the following: power supply terminals, input terminals, output terminals, and com munications terminals (for models with communications). if reinforced insula tion is required, provide additional insulation, such as spacia l distance or material insulation, as defined by iec 60664 suitable for the maximum operating voltage. relay output voltage output terminals 11 to 15 do not exist on models without an option unit (heater burnout detection, control output 2, event inputs, or communications). terminal a pp lications de p end on the model of the o p tion unit. ? + + ? + alarm outputs control output 1 alarm 1/ heater burnout alarm/ input error output (see note.) alarm 2 analog input current output infrared temperature sensor communications/ heater burnout/ ssr failure detection (2-ct input) platinum resistance thermometer communications/ voltage output specification + ? do not connect. voltage output/ heater burnout/ ssr failure detection + ? control output 2 do not connect. event input 1 event input 2 event input/ heater burnout / ssr failure detection heater burnout/ ssr failure detection input heater burnout/ ssr failure detection input voltage output 12 vdc, 21 ma heater burnout/ ssr failure detection input the input power supply depends on the power supply specification of the controller and is either 100 to 240 vac or 24 vac/dc (no polarity). note: output when an input error output is enabled in the advance function setting level. if an input error output is enabled, the a1-1 operation indication on the front panel will not light and s.err will be displayed on the no. 1 display. 6 7 8 9 10 11 12 13 14 15 1 3 2 4 5 11 12 13 14 15 b pt tc a b b a v ma 6 7 8 1 2 1 2 1 2 rs-485 ct1 ct2 11 12 13 14 15 b a rs-485 11 12 13 14 15 11 12 13 14 15 ct1 ct1 ? + 4 to 20 ma dc/ 0 to 20 ma dc ? + 12 vdc 21 ma input power supply control output 2 voltage output 12 vdc, 21 ma e5cn 7 8 9 10 11 1 2 3 4 6 voltage output pt tc alarm 1/ input error output (see note.) control output 1 input power supply do not connect. 7 8 9 alarm 1/ input error output alarm 2/ control output 2 analog input a b b + + + ? ? ? dc12v 21ma 5 4 relay output one alarm output two alarm outputs 5 infrared temperature sensor platinum resistance thermometer the input power supply depends on the power supply specification of the controller and is either 100 to 240 vac or 24 vac/dc (no polarity). order the p2cf-11 or p3ga-11 socket separately. (see page 14.) note: output when an input error output is enabled in the advance function setting level. if an input error output is enabled, the al-1 operation indication on the front panel will not light and s.err will be displayed on the no. 1 display. 0 to 50 mv input only e5cn-u
digital temperature controllers e5cn/e5cn-u 11 nomenclature e5cn e5cn-u the front panel is the same for the e5cn and e5cn-u. dimensions standard models operation indicators level key temperature unit no.1 display no. 2 display up key mode key down key 48 48 terminal cover (e53-cov10) 6 58 44.8 44.8 48.8 91 78 mounting adapter (accessory) 60 min. (48 number of units ? 2.5) +1.0 0 45 +0. 6 0 45 +0.6 0 45 +0.6 0 group mounting does not allow waterproofing. panel cutout mounted separately group mounted e5cn terminal models  recommended panel thickness is 1 to 5 mm.  group mounting is not possible in the vertical direction. (maintain the specified mounting space between controllers.)  to mount the controller so that it is waterproof, insert the waterproof packing onto the controller.  when two or more controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications. 6 14.2 58 70.5 48 48 44.8 44. 8 mounting adapter (accessory) 60 min. (48 number of units ? 2.5) +1.0 0 45 +0.6 0 45 +0.6 0 panel cutout mounted separately group mounted 45 +0.6 0 e5cn-u plug-in models  recommended panel thickness is 1 to 5 mm.  group mounting is not possible in the vertical direction. (maintain the specified mounting space between controllers.)  when two or more controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications.
12 digital temperature controllers e5cn/e5cn-u accessories current transformers (sold separately) 48 48.8 22 9.1 terminal cover e53-cov10 note: the suffix ?500? is added to the model number of each controller provided with a e53-cov10 terminal cover. 30 21 15 5.8 dia. 25 3 40 10.5 2.8 7.5 10 two, 3.5 dia. e54-ct1 40 40 30 12 dia. 9 2.36 dia. 15 30 two, m3 (depth: 4) approx. 3 dia. 18 ( 22 ) approx. 6 dia. plug armature lead e54-ct3 e54-ct3 accessory  armature plug connection example
digital temperature controllers e5cn/e5cn-u 13 adapter note: use this adapter when the panel has already been prepared for the e5b @ . e5cn-u wiring socket (sold separately) note: a model with finger protection (p2cf-11-e) is also available. note: 1. using any other sockets will adversely affect accuracy. use only the specified sockets. 2. a protective cover for finger protection (y92a-48g) is also available. fixture (accessory) 69.6 to 77.6 87 72 72 76 4.7 67 67 y92f-45 panel (1 to 8 mm) 77.3 (to back of e5cn) 72 72 48 48 2.2 4.7 mounted to e5cn 40 0.2 4.5 5 6 7 8 4 3 2 1 9 10 11 70 max. 4 eleven, m3.5 7.5 sems screws 7.8 two, 4.5-dia. holes 50 max. 3 31.2 max. 35.4 note: can also be mounted to a din track. mounting holes terminal layout/internal connections (top view) two, 4.5 dia mounting holes front-connecting socket p2cf-11 5 6 7 8 4 3 2 9 10 11 1 25.6 27 dia. 45 45 4.5 16.3 6.2 47 3 8.7 6 terminal layout/internal connections (bottom view) back-connecting socket p3ga-11
14 digital temperature controllers e5cn/e5cn-u
digital temperature controllers e5cn/e5cn-u 15 operation outline of operation procedures the following diagram illustrates the entire setting level. a password is required to enter the advance function setting level and the calibration level. some parameters may not be displayed depending on the protection settings and operation conditions. the control operation will stop when switching from operation level to initial setting level. ] note: 1. operation level entered for software reset. 2. you cannot move to other levels by operating the keys on the front panel from the calibration level. you must turn off the powe r supply. 3. you can move only to the operation level by operating the keys on the front panel from the manual control level. 4. the time taken to move to the protect level can be adjusted by changing the ?move to protect level time? setting. input password. input password. set value 1201 control in progress control stopped operation level not displayed for some models level change initial setting level communications setting level adjustment level protect level power on press the level key less than 1 s. manual control level press the level key for at least 1 s. starting in manual mode starting in automatic mode manual mode press the level key for at least 1 s. press the level + mode keys. for at least 1 s calibration level press the level + mode keys; display will flash. advanced function setting level (see note 1.) (see note 2.) (see note 3.) a-m c 25 100 c 25 100 c set value ? 169 press the level key for at least 3 s while a-m is displayed. press the level key for at least 1 s; display will flash. press the level key for at least 1 s. press the level key for at least 1 s; display will flash. press the level key for at least 3 s. control stops . press the level + mode keys for at least 3 s. (see note 4.) press the level key for less than 1 s.
16 digital temperature controllers e5cn/e5cn-u parameters operation level manual control level power on adjustment level protect level communications setting level a-m m-sp 0 25 c 25 0 c sp-m 0 c ct1 0.0 ct2 0.0 lcr1 0.0 lcr2 0.0 prst rset sktr 0 r-s run al-1 0 c al1h 0 c al1l 0 c al-2 0 c al2h 0 c al2l 0 c al-3 0 c al3h 0 c al3l 0 c o 0.0 c-o 0.0 process value added when pv display is added. process value/ set point multi-sp set point setting sp ramp monitor heater current value 1 monitor heater current value 2 monitor leakage current value 1 monitor leakage current value 2 monitor program start remaining soak time monitor run/stop alarm value 1 upper-limit alarm value 1 lower-limit alarm value 1 alarm value 2 upper-limit alarm value 2 lower-limit alarm value 2 alarm value 3 upper-limit alarm value 3 lower-limit alarm value 3 mv monitor (heating) mv monitor (cooling) cmwt off ct1 0.0 l.adj at off ct2 0.0 lcr1 0.0 lcr2 0.0 hb1 0.0 hb2 0.0 hs1 50.0 hs2 50.0 sp-0 0 c sp-1 0 c sp-2 0 c sp-3 0 c ins 0.0 c insh 0.0 c p 8.0 c i 233 d 40 c-sc 1.00 c-db 0.0 c of-r 50.0 hys 1.0 c chys 1.0 c soak 1 wt-b off c mv-s 0.0 mv-e 0.0 sprt off c ol-h 105.0 ol-l -5.0 at execute/cancel communications writing ssr failure detection 1 ssr failure detection 2 sp 0 sp 1 sp 2 sp 3 temperature input shift proportional band integral time derivative time cooling coefficient dead band manual reset value hysteresis (heating) hysteresis (cooling) soak time wait band mv at stop mv at pv error sp ramp set value mv upper limit mv lower limit protocol setting communications unit no. baud rate data bits stop bits communications parity send delay psel cwf u-no 1 bps 9.6 len 7 sbit 2 prty even sdwt 20 pmov 0 oapt 0 icpt 1 wtpt off pmsk on prlp 0 move to protect level operation/adjustment protection initial setting/ communications protection setting change protection parameter mask enable password to move to protect level password setting press the level key less than 1 s. press the level key less than 1 s. press the level key for at least 3 s. ( display flashes for at least 1 s.) displays other than that for switching between automatic and manual starting in automatic mode starting in manual mode 25 c pv/mv pid control only insl 0.0 c sp used by multi-sp set either of these parameters. pid settings heating/cooling hysteresis settings 1-point shift 2-point shift compoway/f (sysway) only auto/manual switch pid control only added when auto/manual switching function is added. set either of these parameters. press the level key for at least 1 s. adjustment level display displayed only once when entering adjustment level. a heater current value 1 monitor heater current value 2 monitor leakage current value 1 monitor leakage current value 2 monitor heater burnout 1 detection heater burnout 2 detection upper-limit temperature input lower-limit temperature input clear the offset during stabilization of p or pd control. press the level key for at least 3 s. (display flashes for at least 1 s.) set either of these parameters. set either of these parameters. press the level + mode keys for at least 3 s. display flashes. the time taken to move to the protect level can be adjusted by changing the "move to protect level time" setting. displayed only when a password is set. restricts moving to protect level. restricts displaying and modifying menus in operation, adjustment, and manual control levels. this protect level restricts movement to the initial setting, communications setting, and advanced function setting levels. protects changes to setups by operating the front panel keys. displayed only when a parameter mask is set. switches between compoway/f (sysway) and modbus. displayed only for models with communications. changes are effective after cycling power or after a software reset. press the level + mode keys for at least 1 s. press the level key less than 1 s. a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a some parameters are not displayed depending on the model of the controller and parameter settings. for details, refer to the e5cn/e5cn-u tem perature controller user's manual (cat. no. h129)
digital temperature controllers e5cn/e5cn-u 17 initial setting level advanced function setting level in-l 0 dp 0 in-t 5 in-h 100 d-u c sl-h 1300 c sl-l -200 c cntl onof s-hc stnd st on ptrn off cp 20 c-cp 20 orev or-r alt1 2 alt2 2 alt3 2 tr-t off tr-h 100.0 tr-l 0.0 o1-t 4-20 amov 0 input type scaling upper limit scaling lower limit decimal point temperature unit sp upper limit sp lower limit pid on/off standard or heating/ cooling st program pattern control period (heating) control period (cooling) direct/reverse operation alarm 1 type alarm 2 type alarm 3 type transfer output type transfer output upper limit transfer output lower limit linear current output init off ev-m 1 ev-1 none ev-2 stop mspu off spru m rest a al1n n-o alh1 0.2 c al2n n-o alh2 0.2 c al3n n-o alh3 0.2 c hbu on hbl off hbh 0. 1 st-b 15.0 c alfa 0.65 inf 0.0 pvad off o-dp off ret off a1lt off a2lt off a3lt off prlt 3 sero off cjc on rlrv off colr red pv-b 5.0 c a1on 0 a2on 0 a3on 0 a1of 0 a2of 0 a3of 0 istp ins1 mvse off amad off rt off hsu on hsl off hsh 0.1 lba 0 lbal 8.0 c lbab 3.0 c out1 o out2 none alm1 alm1 alm2 alm2 csel on t-u m alsp sp-m cmov 0 parameter initialization number of multi-sp uses event input assignment 1 event input assignment 2 multi-sp uses sp ramp time unit alarm 1 open in alarm alarm 1 hysteresis alarm 2 open in alarm alarm 2 hysteresis alarm 3 open in alarm alarm 3 hysteresis heater burnout detection heater burnout latch st stable range input digital filter additional pv display mv display automatic return of display mode alarm 1 latch alarm 2 latch alarm 3 latch move to protect level time input error output cold junction compensating method mb command logic switching pv display color pv stable range alarm 1 on delay alarm 2 on delay alarm 3 on delay alarm 1 off delay alarm 2 off delay alarm 3 off delay input shift type additional mv for stop/error rt ssr failure detection ssr failure latch ssr failure hysteresis lba detection time lba detection threshold lba detection width control output 1 assignment control output 2 assignment alarm output 1 assignment alarm output 2 assignment display text switch soak time unit alarm sp selection move to calibration level press the level key less than 1 s. move by setting password ( ? 169). press the level key for at least 1 s. two sps: 1 four sps: 2 for input type of analog limit the set point. set the pulse output cycle. linear output linear output c, f a for input type of temperature for input type of temperature, standard, or pid when assigning pid or control output to pulse output displayed when initial setting/ communications protection is set to 0 move to advanced function setting level heater burnout hysteresis standby sequence reset method auto/manual switching function addition a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
18 digital temperature controllers e5cn/e5cn-u improvements to e5cn functionality changes model numbers have been changed to allow for multi-input specifications. precautions in replacing previous controllers  the input type setting numbers have changed to allow for multi- input specifications. (the default setting is for a k sensor between  200 and 1,300  c.)  previous e5cn controllers cannot be removed from the case for replacement with new models. replace the case at the same time.  the previous thermotools cannot be used with the new controller models. use the thermotools scheduled for marketing from july 2004.  the height of the front panel that extends when the controller is mounted to a panel has been reduced from 9 to 6 mm. note: items that have not been changed  panel cutout dimensions  panel interior dimensions for panel mounting  wiring terminal sizes  wiring terminal arrangement  parameter setting procedure improved functions the previous and new models can be easily diff erentiated by looking at the front panel. the omron logo is in a different positi on. basically, the controllers are upwardly compatible. the terminal arrangement, terminal sizes, and depth for panel mounting have not been changed. changes are listed in the following tables. for details, refer to the e5cn/e5cn-u temperature controller user's manual (cat. no. h129) and to the e5cn temperature controller communications user's manual (cat. no. h130). before change e5cn- @@@ tc (models for thermocouples) e5cn- @@@ p (models for platinum resistance thermometers) after change e5cn- @@@ t (models that support both thermocouples and platinum resistance thermometers) 6 mm item previous models (omron logo: lower left) improved models (omron logo: upper left) front panel the following items do not change in comparison to the previous e5cn models: panel cutout, internal panel dimensions for panel mounting, wiring screw sizes, wiring terminal arrangement, and parameter setting methods. alm1 alm2 hb out1 out2 stop cmw
digital temperature controllers e5cn/e5cn-u 19 specifications ratings item previous models improved models power consumption e5cn 7 va (100 to 240 vac, 50/60 hz) 4 va/3 w (24 vac, 50/60 hz or 24 vdc) 7.5 va (100 to 240 vac, 50/60 hz) 4 va/3 w (24 vac, 50/60 hz or 24 vdc) e5cn-u 6 va (100 to 240 vac, 50/60 hz) 3 va/2 w (24 vac, 50/60 hz or 24 vdc) 6 va (100 to 240 vac, 50/60 hz) 3 va/2 w (24 vac, 50/60 hz or 24 vdc) sensor input e5cn- @@ tc thermocouple: k, j, t, e, l, u, n, r, s, or b infrared temperature sensor: 10 to 70  c, 60 to 120  c or 115 to 165  c (160 to 260  c) voltage input: 0 to 50 mv e5cn- @@ t (multi-input models) thermocouple: k, j, t, e, l, u, n, r, s, or b infrared temperature sensor: 10 to 70  c, 60 to 120  c or 115 to 165  c (160 to 260  c) voltage input: 0 to 50 mv platinum resistance thermometer: pt100 or jpt100 e5cn- @@ p platinum resistance thermometer: pt100 or jpt100 (no models with analog inputs) e5cn- @@ l (models with analog inputs added.) current input: 4 to 20 ma or 0 to 20 ma voltage input: 1 to 5 v, 0 to 5 v, or 0 to 10 v control output relay e5cn-r @@ spst-no, 250 vac, 3 a (resistive load) electrical life: 100,000 operations min. e5cn-r @@ spst-no, 250 vac, 3 a (resistive load) electrical life: 100,000 operations min. --- e5cn-y @@ (added models with long-life relay outputs.) (to be available soon) spst-no, 250 vac, 3 a (resistive load) electrical life: 1,000,000 operations min. dc loads cannot be connected. vo ltag e e5cn-q @@ 12 vdc  15% (pnp) max. load current: 21 ma with short-circuit protection e5cn-q @@ 12 vdc  15% (pnp) max. load current: 21 ma with short-circuit protection current e5cn-c @@ 4 to 20 ma dc load: 600  max. resolution: approx. 2,600 e5cn-c @@ 4 to 20 ma dc or 0 to 20 ma dc load: 600  max. resolution: approx. 2,700 control output 2 vo ltag e (no models with two control outputs) (option unit) 12 vdc  15% (pnp) max. load current: 21 ma with short-circuit protection display method 7-segment digital display and single-led indicators character height: pv: 9.9 mm, sv: 6.4 mm 11-segment digital display and single-led indicator (improved visibility) (a 7-segment digital display also possible.) character height: pv: 11.0 mm, sv: 6.5 mm transfer output (no models with transfer outputs) e5cn-c @@ (current output) allocated to current output 4 to 20 ma dc or 0 to 20 ma dc load: 600  max. resolution: approx. 2,700
20 digital temperature controllers e5cn/e5cn-u other functions characteristics communications specifications heater burnout/ssr failure detection characteristics item previous models improved models display --- parameter mask function (provided with setting software) pv display switch between 2 colors (red/green) pv display switch between 3 colors (red/orange/green) --- display character switch (7-segment/11-segment) input temperature input shift (1-point shift for temperature input, 2-point shift for no-contact sensor input) temperature input shift (2-point shift also possible for temperature input) output --- manual outputs --- mv at stop --- mv at pv error --- loop break alarm control control period: 1 to 99 s control period: 0.5 or 1 to 99 s --- robust tuning alarm --- alarm delays --- alarm sp selection (selection of alarm operation of sp indicator) other --- simple programming function --- password to move to protect level --- setting software port item previous models improved models sampling period 500 ms 250 ms item previous models improved models communications protocols compoway/f (sysway) compoway/f (sysway), modbus baud rate 1200, 2400, 4800, 9600, 19200 bps 1200, 2400, 4800, 9600, 19200, 38400 bps item previous models improved models maximum heater current option units single-phase 50 a vac option units single-phase 50 a ac --- option units (two ct inputs) three-phase 50 a ac ssr failure detection --- ssr failure detection
digital temperature controllers e5cn/e5cn-u 21 precautions note: refer to the ntlp: electronic temperature controller catalog (cat. no. ntlp) for common precautions. note: 1. an selv circuit is one separated from the power supply with double insulation or reinforced insulation, that does not exceed 30 v r.m.s. and 42.4 v peak or 60 vdc. 2. a class 2 power supply is one tested and certified by ul as have the current and voltage of the secondary output restricted to specific levels. precautions for safe use 1. do not use the temperature controller in the following locations.  locations exposed to radiated heat from heating devices  locations subject to exposure to water or oil  locations subject to direct sunlight  locations subject to dust or corro sive gas (especially sulfide gas or ammonia gas).  locations subject to se vere temperature changes  locations subject to icing or condensation  locations subject vibr ation or strong shock 2. use and store the temperature controller within the rated ambient temperature and humidity. when two or more temperature controllers are mounted horizontally close to each other or vertically next to one another, the internal temperature will increase due to heat radiated by the temperature controllers and the service life will decrease. in such a case, use forced cooling by fans or other means of air ventilation to cool down the temperature controllers. 3. allow enough space around the temperature controller to ensure proper heat dissipation. do not block the ventilating holes. 4. be sure to wire terminals properly using the correct polarity. 5. use crimp terminals with the specified dimensions (m3.5, width 7.2 mm max.). use wires of a thickness of awg24 (0.205 mm 2 ) to awg14 (2.081 mm 2 ). the exposed current-carrying part to be inserted into terminals must be 5 to 6 mm. 6. do not connect anything to unused terminals. 7. allow as much space as possible between the controller and devices that generate powerful high frequencies (high-frequency welders, high-frequency sewing machines, etc.) or surge. keep the wiring for the temperature controller's terminal block away from power cables carry high voltages or large currents. also, do not wire power lines together with or parallel to temperature controller wiring. 8. use the temperature controller within a power supply voltage and load that meet all specifications and ratings. 9. set up the power supply so that the voltage will reach the rated voltage within 2 seconds after turning on. 10. allow at least 30 minutes for the temperature controller to warm up. 11. when using self-tuning, turn on power for the load (e.g., heater) at the same time as or before supplying power to the temperature controller. 12. install the appropriate switches and circuit breakers and label them accordingly so that power can be turned off in an emergency by the person operating the temperature controller. 13. if you remove the controller from its case, do not touch or apply shock to the electronic parts inside. when placing the controller back in the case, make sure that electronic parts do not come in contact with the case. 14. use alcohol to clean the temperature controller. do not use thinner or other solvent-based substances. 15. it will require 2 seconds for the outputs from the temperature controller to stabilize after turning on the power supply. design the system (e.g., the control panel) to allow for this time. 16. outputs will turn off depending on the mode when switching to the initial setting mode. confirm system safety before switching the mode. do not touch any of the terminals while the power is being supplied. doing so may occasionally result in minor electric shock. do not allow pieces of metal or wire cuttings to get inside the temperature controller. failure to do so may occasionally result in minor electric shock, fire, or damage to equipment. do not use the temperature controller in locations subject to flammable or ex plosive gas. doing so may occasionally result in minor injury due to explosion. do not attempt to disassemble, modify, or repair the temperature controller or touch any internal components. doing so may occasionally result in minor electric shock, fire, or damage to equipment. caution: danger of electric shock a) this temperature contro ller is ul-listed as an open- type process controller. use it in a control panel structure so that fire will not leave the panel. b) when using two or more cutoff switches, turn off all switches so that no power is supplied to the temperature controller before maintenance or inspections. c) signal inputs are selv restricted circuits. (see note 1.) d) caution: to reduce the danger of fire or electric shock, do not internally connect the outputs of different class 2 circuits. (see note 2.) if the output relay is used beyond its life expectancy, its contacts may occasionally become fused or burned. always consider the actual application conditions and be sure to use the output relay within its rated load and electrical life expectancy. the life expectancy of the output relay varies considerably according to its switching capacity and operating conditions. fire may occasionally occur if terminal screws become loose. tighten the terminal screws using a torque between 0.74 and 0.90 nm. make settings for the temperature controller that are suitable for the controlled system. failure to do so may result in unexpected operation occasionally resulting in damage to equipment or personal injury. warning: to reduce the danger or electric shock or fire, use the temperature controller in an controlled environment relatively free from polluting materials. take appropriate safety meas ures, such as installing a separate monitoring system, to ensure safe operation in the event of a malfunction of the temperature controller. loss of operation control or alarm outputs due to malfunction may occasionally result in physical damage to the controlled system or equipment. ! caution
22 digital temperature controllers e5cn/e5cn-u precautions for correct use service life 1. use the temperature controller within the following temperature and humidity ranges: temperature:  10 to 55  c (with no icing or condensation) humidity: 25% to 85% if the controller is installed inside a control board, the ambient temperature must be kept to under 55  c, including the temperature around the controller. 2. the service life of electronic devices like temperature controllers is determined not only by the number of times the relay is switched but also by the service life of internal electronic components. component service life is affected by the ambient temperature: the higher the temperature, the shorter the service life and, the lower the temperature, the longer the service life. therefore, the service life can be extended by lowering the temperature of the temperature controller. 3. when two or more temperat ure controllers are mounted horizontally close to each other or vertically next to one another, the internal temperature will increase due to heat radiated by the temperature controllers and the service life will decrease. in such a case, use forced cooling by fans or other means of air ventilation to cool down the temperature controllers. when providing forced cooling, however, be careful not to cool down the terminals sections alone to avoid measurement errors. measurement accuracy 1. when extending or connecting the thermocouple lead wire, be sure to use compensating wires that match the thermocouple types. 2. when extending or connecting the lead wire of the platinum resistance thermometer, be sure to use wires that have low resistance and keep the resistance of the three lead wires the same. 3. mount the temperature controller so that it is horizontally level. 4. if the measurement accuracy is low, check to see if input shift has been set correctly. waterproofing the degree of protection is as shown below. sections without any specification on their degree of protection or those with ip @ 0 are not waterproof. front panel: nema4x for indoor use (equivalent to ip66) rear case: ip20, terminal section: ip00 (e5cn-u: front panel: equivalent to ip50, rear case: ip20, terminals: ip00) operating precautions 1. it takes approximately two seconds for the outputs to turn on from after the power supply is turned on. due consideration must be given to this time when incorporating temperature controllers in a sequence circuit. 2. when using self-tuning, turn on power for the load (e.g., heater) at the same time as or before supplying power to the temperature controller. if power is turned on for the temperature controller before turning on power for the load, self-tuning will not be performed properly and optimum control will not be achieved. 3. when starting operation after the temperature controller has warmed up, turn off the power and then turn it on again at the same time as turning on power for the load. (instead of turning the temperature controller off and on again, switching from stop mode to run mode can also be used.) avoid using the controller in places near a radio, television set, or wireless installing. 4. these devices can cause radio disturbances which adversely affect the performance of the controller. mounting mounting to a panel 1. to mount the controller so that it is waterproof, insert the waterproof packing onto the controller. group mounting does not allow waterproofing. the waterproof packing is not required if waterproofing is not necessary. the panel mounting adapter is also included with the e5cn-u. waterproof packing is not included with the e5cn-u. 2. insert the e5cn/e5cn-u into the mounting hole in the panel. 3. push the adapter along the controller body from the terminals up to the panel, and fasten it temporarily. 4. tighten the two fixing screws on the adapter. alternately tighten the two screws a little at time to keep them balanced. tighten them to a torque of 0.29 to 0.39 nm. attaching the terminal cover make sure that the ?up? letters on the e5cn are at the top and insert the terminal cover into the holes at the top and bottom of the controller. removing the controller from the case when carrying out maintenance on the controller, the controller can be removed from the case with the terminal leads still attached. the controller can be removed from the case only with the e5cn. it cannot be removed with the e5cn-u. 1. insert the tool into the slots (one on the top and one on the bottom) and release the hooks. 2. insert the tool into the gap between the front panel and rear case and pull out the front panel slightly. hold both sides of the front panel and draw out the controller towards you. do not apply unnecessary force. 3. before inserting the controller, confirm that the sealing rubber is in place. insert the controller into the rear case until you hear a click. press on the hooks on the top and bottom of the rear case to be sure that the hooks are securely locked in place.be sure that electronic parts do not come in contact with the case. terminal cover (order separately) mounting adapter (accessory) e5cn e5cn-u waterproof packing panel order the p2cf-11 or p3ga-11 socket separately. front-mounting socket (panel mounting is also possible.) 20 min. 0.4 2.0 e 5 c n pv sv a l m 1 a l m 2 a lm 3 h a o u t 1 s to p o u t 2 c m w m a n u (1) (1) (2) (3) tool insertion hole flat-blade screwdriver (unit: mm)
digital temperature controllers e5cn/e5cn-u 23 wiring precautions  separate input leads and power lines to protect the controller and its lines from external noise.  use wires of a thickness of awg24 (0.205 mm 2 ) to awg14 (2.081 mm 2 ). the exposed current-carrying part to be inserted into terminals must be 5 to 6 mm.  we recommend using crimp terminals when wiring the terminals.  tighten terminal screws to a torque of 0.74 to 0.90 nm.  use the following type of crimp terminals for m3.5 screws. 7.2 mm min. 7.2 mm min.
24 in the interest of product improvement, specifications are subject to change without notice. all dimensions shown are in millimeters. to convert millimeters into inches, multiply by 0. 03937. to convert grams into ounces, multiply by 0.03527. cat. no. h128-e1-01 omron corporation industrial automation company industrial devices and components division h.q. measuring components department shiokoji horikawa, shimogyo-ku, kyoto, 600-8530 japan tel: (81)75-344-7080/fax: (81)75-344-7189 printed in japan 0404-??m (0404) (?) warranty and appli cation considerations read and understand this catalog please read and understand this catalog before purchasing the products. please consult your omron representative if you have any questions or comments. warranty and limitations of liability warranty omron's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by omron. omron makes no warranty or representation, express or implied, regarding non-infringement, merchantability, or fitness for particular purpose of the products. any buyer or user acknowledges that the buyer or user alone has determined that the products will suitably meet the requirements of their intended use. omron disclaims all other warranties, express or implied. limitations of liability omron shall not be responsible for special, indirect, or consequential damages, loss of profits, or commercial loss in any way connected with the products, whether such claim is based on contract, warranty, negligence, or strict liability. in no event shall the responsibility of omron for any act exceed the individual price of the product on which liability is asse rted. in no event shall omron be responsible for warranty, repair, or other claims regarding the products unless omron's analysis confirms that the products were properly handled, stored, installed, and maintained and not subject to contamination, abuse, misuse, or inappropriate modification or repair. application considerations suitability for use omron shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's application or use of the products. take all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it wil l be used. know and observe all prohibitions of use applicable to this product. never use the products for an application involving serious risk to life or property without ensuring that the system as a whole has been designed to address the risks, and that the omron products are properly rated and installed for the intended use within the overall equipment or system. disclaimers performance data performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. it may represent the result of omron's test conditions, and the users must correlate it to actual application requirements. actual performance is subject to the omron warranty and limitations of liability. change in specifications product specifications and accessories may be changed at any time based on improvements and other reasons. consult with your omron representative at any time to confirm actual specifications of purchased product. dimensions and weights dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.


▲Up To Search▲   

 
Price & Availability of E5CN-C2ML-500

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X